Unit Coordinated Control for Drum Boilers
The Ovation® expert control system offers Unit
Coordinated Control (UCC) that provides a
coordinated front-end control strategy that unites
the boiler and turbine controls. Coordinated
controls generate and regulate the setpoint for
unit load (MW). The unit load setpoint or UCC
MW Demand may be generated from local
operator entry, remote increase/decrease
contact inputs, or internally generated
contingencies such as runbacks and rundowns.
Unit coordinated control manages unit load
(megawatts) and throttle pressure by sending
out parallel demand signals to the boiler and
turbine control loops through the Boiler Master
and Turbine Master M/A Stations, respectively.
The Boiler Master demand is used as a feedforward
signal to the loops controlling feedwater,
fuel and air flow to improve unit response to load
changes.
The Turbine Master demand controls
the turbine control valves by sending an analog
output signal to the turbine controls.
The operator interface to the unit control is
through a dedicated graphic and associated
pop-up windows which may be accessed at an
Operator’s station.
Features
- Provides a coordinated front-end control strategy that unites boiler and turbine controls
- Offers air/fuel cross limiting to regulate the fuel and air input in response to load changes
- Offers typical air flow control stations, furnace pressure control stations (ID fans), and feedwater control stations